512 MB non-volatile flash memory for stable data storage. Power: 24 VAC @ 5–26 VA depending on connected loads. Core Benefits
: Requires an external, precision 250-ohm resistor installed across terminals to convert current loops to voltage drops.
Uncontrolled 24 VDC output (up to 100 mA) to power external transducers Input Hardware Capabilities
The Alerton VLC-1600 is designed primarily to monitor inputs, offering high-resolution inputs to track building variables. It is a native BACnet device, making it easy to integrate into existing BACnet MS/TP networks. While it does not feature control outputs (making it purely a monitoring device), it offers 16-bit universal inputs (UIs) that can be configured for a variety of sensors. vlc 1600 datasheet
: Screw mounting is executed via predefined layout positions outlined in the Honeywell VisualLogic Controller Installation Manual . It shares the exact mechanical footprint, hole pattern, and dimensions as sibling models like the VLC-853, VLC-550, and VLC-660R.
: Removable header-type screw terminals that accept 14–24 AWG wire. www.acontrols.co.za or details on its VisualLogic programming? hbt-bms-VLC-1600-E-datasheet.pdf
The physical form factor of the VLC-1600 uses an open-board style configuration that must be safely mounted inside a secure, lockable control panel enclosure. 512 MB non-volatile flash memory for stable data storage
The sensor is available in two primary output configurations:
Communicates directly on a BACnet MS/TP LAN at speeds up to 115.2 Kbps.
Extensive monitoring allows facility managers to detect energy waste. Uncontrolled 24 VDC output (up to 100 mA)
: Header-type screw terminals are removable and accept 14–24 AWG wire, drastically simplifying field wiring and unit replacements.
: Safely enables a single transformer to power multiple VLC modules in parallel.